Inverter Application Example
Machine
name Roof fan Classification Fan and pump No. AP-E-02
Application Building ventilation Similar application Ventilation fans of various types
<<Purpose>> Noises from the fan for the range hood exhaust is reduced.
<<Effect>> Complains of noises by the people on the upper floors of a building is eliminated at nighttime.
<<Composition>>
Ventilation roof fan (multi units)
Inverter panel
Range hood
<<Outline and points of operation>>
Since noises are not a problem during daytime, the fan
speed is reduced to lower the noise only during nighttime.
A timer is used to control the rotation speed in order to
reduce the need for manual control.
<<Specifications required>>
• Multiple fans on the roof
• One inverter is used for control.
<<Advantages of inverter application>>
Since the speed is varied as desired, it can be easily
changed according to the number of unit in the building.
<<Points to care>>
(1) In order to reduce the noise, it is necessary to use a
low audible noise type inverter.
(2) It is necessary to install the radio noise filter for
electrical noise countermeasure.
(3) If any inverter storage is installed on the roof (outdoor),
it is important to take a countermeasure against the
elements.
Issued date: February, 2001
Mitsubishi Electric, Nagoya Works Inverter Engineering Section