07_LH4_N1_N2_soft_starters_cat.pdf

(774 KB) Pobierz
Soft starters
Selection guide
0
<< Back
Applications
Starting simple machines
Power range for 50…60 Hz supply (kW)
0.75…11
1.1…75
Single phase 208…240 V (kW)
0.75…3
3-phase 208…240 V (kW)
1.1…5.5
1.1…22
3-phase 230…415 V (kW)
3-phase 380…415 V (kW)
3…11
3…45
3-phase 440…480 V (kW)
3…11
3…45
3-phase 440…500 V (kW)
3-phase 208…690 V (kW)
7.5…75
Output frequency
50/60 Hz
Control profile
Voltage ramp
Energy saving
Integrated bypass
Communication
Integrated serial link
Industrial buses and networks
AS-i
Degree of protection
IP 20
Dialogue
2 integrated LEDs
PowerSuite software workshop
Incompatible
References
LH4 N1
LH4 N2
Pages
24075/2
Schneider Electric
809960021.091.png 809960021.102.png 809960021.113.png 809960021.124.png 809960021.001.png 809960021.011.png 809960021.022.png 809960021.033.png 809960021.044.png 809960021.049.png 809960021.050.png 809960021.051.png 809960021.052.png
 
Presentation
Soft starters
1
LH4 soft start units - open version
Presentation
Asynchronous motors are widely used because they are robust, reliable, standardised and inexpensive. Starting this type
of motor has always required a careful compromise between the cost of the starter unit and performance:
- torque peaks which may damage the mechanics,
- current peaks on power up,
- significant line voltage drops.
The LH4-N1 starting torque controller is used for single-phase and 3-phase motors whenever surges caused on starting
need to be suppressed. It can only be used with low-power motors.
The LH4-N2 soft start - soft stop unit can be used to control starting torque and soft stops, while significantly reducing
starting current.
LH4-N244Q7
Principle, use
Unlike electromechanical starters, LH4 electronic starters can be used to adjust starting torque, thus eliminating
mechanical shocks which result in increased wear, maintenance and production downtime.
LH4-N1 soft start units are recommended for use with conveyors, conveyor belts, fragile or noisy automatic doors, drag
lifts, small gantries such as those used in car washes and all machines equipped with drive belts.
LH4-N2 soft start - soft stop units are used for fans, pumps, cold compressors, compressed air equipment and all types
of high inertia machinery. On machines which do not require electrical isolation, they eliminate the need for a line
contactor.
LH4-N2 units, which give higher performance, can be used instead of LH4-N1 units.
Operation
LH4 soft start units start with reduced voltage. The voltage rises gradually until it reaches its rated value. This reduces
torque surges which can be harmful both to the motor and to the mechanism being driven, and also reduces starting
currents (with the LH4-N2).
The user can adjust the starting torque using one of the LH4 potentiometers.
Starting time can also be adjusted via the second potentiometer.
The motor connected to the LH4 must be able to start the load at reduced voltage.
A third potentiometer on LH4-N2 units can be used to adjust deceleration time.
LH4-N285Q7
On the LH4-N2, a relay, which indicates product faults and can be used to control the line contactor (isolation), gives a
signal when the product is operating. This signal can be used to control the line contactor.
Once the starting process has finished, a relay or contactor integrated in the LH4 shunts the electronics limiting
electromagnetic interference and temperature rises. This contactor drops out on the stop request, whether deceleration
takes place or not.
For the LH4-N230 rating and above, end of starting data can be obtained by adding an attachment which can be mounted
on the electronics shunting contactor without dismantling the product.
Description of the range
The range of LH4-N soft start units comprises 2 product families:
- LH4-N1 units, comprising 3 ratings from 6 to 22 A,
- LH4-N2 units, comprising 7 ratings from 6 to 85 A.
The following products are designed for 3-phase voltages (the LH4-N1 can also operate in single phase):
- 230, 400 and 460 V at 50 or 60 Hz for ratings up to 22 A,
- 200 to 690 V and 400 V at 50 or 60 Hz for ratings from 32 to 85 A.
The maximum power for start units, at an operating voltage of 400 V, is 45 kW.
Adjustments and start-up
All start and stop units have 2 potentiometers which can be used to:
- adjust acceleration time,
- obtain the starting torque required for an immediate start following the run signal.
On LH4-N2 units, there is a third potentiometer for adjusting deceleration time.
These functions can be sealed to avoid the risk of settings being lost.
Characteristics:
page s 24071/3 t o 24071/5
References:
pa ges 24075/2 and 24075/3
Dimensions:
page 24076/2
Schemes:
pa ges 24076/3 to 24076/5
24071-EN_Ver4.2.fm/2
Schneider Electric
809960021.053.png 809960021.054.png 809960021.055.png 809960021.056.png 809960021.057.png 809960021.058.png 809960021.059.png 809960021.060.png 809960021.061.png 809960021.062.png 809960021.063.png 809960021.064.png 809960021.065.png 809960021.066.png 809960021.067.png 809960021.068.png 809960021.069.png 809960021.070.png 809960021.071.png 809960021.072.png
 
Characteristics
Soft starters
1
LH4 soft start units - open version
Environment
Rated insulation voltage (Ui)
Conforming to IEC 947
V
690
Rated impulse withstand
voltage (Uimp)
Conforming to IEC 947
kV
6 and 8 for LH4-N2ppLY7 products
Conforming to standards
IEC 60947-4-2
Product certifications
ECC (low voltage and EMC) - UL - CSA
Degree of protection
IP 20 (front panel)
Maximum relative humidity
93 % without condensation or dripping water
Maximum ambient pollution
Degree 3 conforming to IEC 664-1 and UL 508
Ambient air temperature
For operation
° C
0…+ 40 with derating of 1.2 % per °C above 40 °C and up to 60 °C
around the device
0...+ 55 for LH4-N2 from 32 A.
For storage
° C
- 25…+ 70
Maximum operating altitude
m
2000 - (above this, derate the power by 0.5 % for each additional 100 m)
Operating positions
Without derating
± 30° in relation to the vertical for permanent operation, any position for
temporary operation.
Shock resistance
Conforming to IEC/EN 68-2-27
8 gn, 11 ms
Vibration resistance
Conforming to IEC/EN 68-2-6
2gn
Immunity to radiated
Conforming to IEC/EN 60947-4-2
Conforming to EN 61000-4-3 level 3
radioelectric interference
Radiated and conducted emissions
Conforming to IEC/EN 60947-4-2
Conforming to EN 61000-4-6 level 3
Electrostatic discharge
Conforming to IEC/EN 60947-4-2
Conforming to EN 61000-4-2 level 3 and EN 55011
Immunity to electrical transients
Conforming to IEC/EN 60947-4-2
Conforming to EN 61000-4-4 level 4
Voltage/current shock wave
Conforming to IEC/EN 60947-4-2
Conforming to EN 61000-4-5 level 3
Radio frequency emissions
Conforming to IEC/EN 60947-4-2
According to CISPR 11 and EN 55011 class A
Output relay characteristics
Rated operating current
Conforming to IEC 947-5-1
Category of use AC-15: Ie 3 A, Ue 250 V
CategoryofuseDC-13:Ie2A,Ue24V
Rated power of contacts
a 250 V
VA
2000 (6 A-250 V)
Minimum switching capacity
17 V
mA
10
Conventional thermal current
A
6
Maximum operating voltage
z 50/60 Hz
V
250
gG type fuse protection
IEC 947-5-1
Presentation:
page 24071/2
References:
pag es 24075/2 a nd 24075/3
Dimensions:
page 24076/2
Schemes:
page s 24076/3 to 24076/5
Schneider Electric
24071-EN_Ver4.2.fm/3
809960021.073.png 809960021.074.png 809960021.075.png 809960021.076.png 809960021.077.png 809960021.078.png 809960021.079.png 809960021.080.png 809960021.081.png 809960021.082.png 809960021.083.png 809960021.084.png
 
Characteristics (continued)
Soft starters
1
LH4 soft start units - open version
Type o f starter
LH4-N106 ppp
LH4-N112 ppp
LH4-N125 ppp
Electrical characteristics
Rated operating voltage (Ue)
V
200…240 ( LH4-N1 pp LU7 ), 380…415 ( LH4-N1 pp QN7 ),
440…480 ( LH4-N1 pp RT7 ) with - 15…+ 10 % on all values
Control voltage
Internal to the product
Frequency
Hz
50 or 60
Rated operating current
A
6
12
22
Starting time
Voltage ramp
s
Adjustable from 1 to 5
Stopping time
Voltage ramp
s
Starting torque
Adjustable from 0.3 to 0.8 of the direct motor starting torque
Power loss
At full load
W
2
3
3.5
at the end of starting
Transient operation
W
20
39
70
Average duty 10%
W
2.5
3.6
4.3
Protection against short-circuits
Type 1 and 2 coordination
A
See list of required parts, pages 24077/2 and 24077/3
Starting and stopping current
Max duty of 360 seconds
A
18
36
75
of starting and stopping
per hour
LED displays
Green
Lit, device powered up
Ye l lo w
Lit, full speed
Logic inputs
mA
Connection
Power circuit
Flexible cable, no sleeve
1 conductor
mm 2
1.5…6
1.5…6
1.5…6
2 conductors
mm 2
1.5…6
1.5…6
1.5…6
Flexible cable with sleeve
1 conductor
mm 2
1.5…4
1.5…4
1.5…4
2 conductors
mm 2
1.5…4
1.5…4
1.5…4
Rigid cable
1 conductor
mm 2
1.5…6
1.5…6
1.5…6
2 conductors
mm 2
1.5…6
1.5…6
1.5…6
Control circuit
Flexible cable, no sleeve
1 conductor
mm 2
2 conductors
mm 2
Flexible cable with sleeve
1 conductor
mm 2
2 conductors
mm 2
Rigid cable
1 conductor
mm 2
2 conductors
mm 2
Earth connection
Presentation:
page 24071/2
References:
pa ges 24075/2 and 24075/3
Dimensions:
page 24076/2
Schemes:
pa ges 24076/3 to 24076/5
24071-EN_Ver4.2.fm/4
Schneider Electric
809960021.085.png 809960021.086.png 809960021.087.png 809960021.088.png 809960021.089.png 809960021.090.png 809960021.092.png 809960021.093.png 809960021.094.png 809960021.095.png 809960021.096.png 809960021.097.png 809960021.098.png 809960021.099.png 809960021.100.png 809960021.101.png 809960021.103.png 809960021.104.png 809960021.105.png 809960021.106.png 809960021.107.png 809960021.108.png 809960021.109.png 809960021.110.png 809960021.111.png 809960021.112.png 809960021.114.png 809960021.115.png 809960021.116.png 809960021.117.png 809960021.118.png 809960021.119.png 809960021.120.png 809960021.121.png 809960021.122.png 809960021.123.png 809960021.125.png 809960021.126.png 809960021.127.png 809960021.128.png 809960021.129.png 809960021.130.png 809960021.131.png 809960021.132.png 809960021.133.png 809960021.134.png 809960021.002.png 809960021.003.png 809960021.004.png 809960021.005.png 809960021.006.png
 
1
LH4-N206 ppp
LH4-N212 ppp
LH4-N225 ppp
LH4-N230 ppp
LH4-N244 ppp
LH4-N272 ppp
LH4-N285 ppp
200…240 ( LH4-N2 pp LU7 ), 380…415 ( LH4-N2 pp QN7 ),
400 ( LH4-N2 pp Q7 ), 200…690 ( LH4-N2 pp LY7 )
440…480 ( LH4-N2 pp RT7 ) with - 15…+ 10 % on all values
with - 15…+ 10 % on all values
Internal to the product, except on LH4-N2ppLY7 units, which must be supplied externally with 115 V/50 or 60 Hz (approximately 20 VA)
50 or 60
6
12
22
32 (5 minimum)
44 (5 minimum)
72 (16 minimum)
85 (16 minimum)
Adjustable from 1 to 5
Adjustable from 1 to 25
Adjustable from 0 to 5
Adjustable from 0 to 25
Adjustable from 0.3 to 0.8 of the direct motor starting torque
3
4
5
22
22
23
23
40
76
130
184
268
436
514
4
6
8
37
44
59
66
See list of required parts, pages 24077/2 and 24077/3
18
36
75
90
132
216
255
Lit, device powered up
Lit, full speed
Logic state 1: I < 10 - Logic state 0: I > 3
Voltage supplied by the product 24 V
±
25 % (no power available)
1.5…6
1.5…6
1.5…6
6...25
6...25
6...25
6...25
1.5…6
1.5…6
1.5…6
6...25
6...25
6...25
6...25
1.5…4
1.5…4
1.5…4
4...25
4...25
4...25
4...25
1.5…4
1.5…4
1.5…4
4...16
4...16
4...16
4...16
1.5…6
1.5…6
1.5…6
6...35
6...35
6...35
6...35
1.5…6
1.5…6
1.5…6
6...25
6...25
6...25
6...25
0.75…2.5
0.75…2.5
0.75…2.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
1…2.5
1…2.5
1…2.5
0.75...1.5
0.75...1.5
0.75...1.5
0.75...1.5
0.75…1.5
0.75…1.5
0.75…1.5
0.75…1.5
Tin-coated terminal. Fixed with ø 6 screws
Schneider Electric
24071-EN_Ver4.2.fm/5
809960021.007.png 809960021.008.png 809960021.009.png 809960021.010.png 809960021.012.png 809960021.013.png 809960021.014.png 809960021.015.png 809960021.016.png 809960021.017.png 809960021.018.png 809960021.019.png 809960021.020.png 809960021.021.png 809960021.023.png 809960021.024.png 809960021.025.png 809960021.026.png 809960021.027.png 809960021.028.png 809960021.029.png 809960021.030.png 809960021.031.png 809960021.032.png 809960021.034.png 809960021.035.png 809960021.036.png 809960021.037.png 809960021.038.png 809960021.039.png 809960021.040.png 809960021.041.png 809960021.042.png 809960021.043.png 809960021.045.png 809960021.046.png 809960021.047.png 809960021.048.png
 