Easy Cabling and Cascading of Drives
(with S7-224 XP, 4x SINAMICS G110 and TP 170micro)
Micro Automation Set 26
V1.0 (Version 07/2004)
Preamble
Micro Automation Sets are fully functional and tested automation configurations based
on A&D standard products for simple, fast and inexpensive automation tasks for small-
scale automation. Each of these Micro Automation Sets covers a frequently used
subtask of a typical customer automation task in the low-end range.
The sets help the customer answer the following questions for these subtasks: “Which
products do I need?” and “How do the products work together?”
However, depending on the requirements of the system, a variety of other
components (e.g., other CPUs, power supplies, etc.) can be used to implement the
functionality on which this set is based. See respective SIEMENS A&D catalogs for
these components.
Warranty/Disclaimer of Liability
These software samples do not purport to cover all details or variations in equipment, nor do
they provide for every possible contingency. The software samples are no customer specific
solution. Every user is responsible for proper operation of the described products. These
software samples do not relieve you of the responsibility to use sound practices in application,
installation, operation and maintenance. By using these software samples, you acknowledge
that Siemens shall not be liable under any theory for damages or personal injury resulting from
such use.
Siemens reserves the right to make changes in these software samples at any time without
notice or obligation. Should a conflict arise between the suggestions in these software samples
and other Siemens publications such as the S7-200 Programmable Controller System Manual
or the SIMATIC S7 / M7 / C7 Programmable Controllers Catalog ST 70, the other publication
shall take precedence.
Copyright© 2000 Siemens A&D. Any form of duplication or distribution of these software
samples or excerpts hereof is prohibited without the expressed consent of Siemens Energy &
Automation, Inc.
404963916.006.png
Easy Cabling and Cascading of Drives (with S7-200, 4x SINAMICS G110)
1
Required Components
Products
Component
Type
MLFB / Order information
No. Manufacturer
CPU
S7-CPU 224 XP DC
6ES7 214-2AD23-0XB0
1
SIEMENS A&D
Micro panel
TP 170micro
6AV6640-0CA01-0AX0
1
Power supply
LOGO! Power 24V/1.3A
6EP1331-1SH02
1
Inverter
SINAMICS G110 120W
without filter; USS version, FS A,
6SL3211-0AB11-2UB0
4
Control device
SINAMICS
BOP
6SL3255-0AA00-4BA0
min. 1
Low-voltage motor
4-pole, aluminium frame, 120W 1LA7060-4AB10
4
Accessories
Component
Type
MLFB / Order information
No. Manufacturer
Profibus cable
(connects inverter with
controller)
PB FC standard, 2-wire bus line,
shielded, delivery packaging:
max. 1000m, minimum: 20m
(supplied by the meter)
SIEMENS A&D
6XV1830-0EH10
Length
[m]
PROFIBUS connector with PG connection
6ES7972-0BB12-0XA0
1
Adapter
for attachment of the SINAMICS
inverter FS A to the top hat rail
6SL3261-1BA00-0AA0
4
(optional)
Filter
(e.g. for operation at the
FI protective switch)
for low leakage currents
6SE6400-2FL01-0AB0
4
(optional)
Inductor
commutation inductor
(optional)
Cable
TP 170micro to CPU
6XV1830-1CH30
1
Note
When simultaneously connecting PG/PC and TP 170micro (and frequency
inverters) to the controller, do not use the "TP 170micro to CPU" connecting
cable specified in the 'Accessories' list. For this purpose, a Profibus cable must
be prepared individually.
Order two Profibus connectors instead of only one specified in the "Accessories"
list and correspondingly more Profibus cable as well.
Note
The configuration, as it is, is intended for industrial application. For energy
supply, industrial networks are usually implemented here. It is therefore not
necessary to use special filters/inductors with low leakage currents.
If the configuration is used in sensible networks (e.g. PCs on the same network),
filters or inductors should be used.
Configuration software/tools
Component
Type
MLFB / Order number
No. Manufacturer
STEP 7Micro/WIN
32
V4.0
6ES7810-2BC02-0YX0
1
SIEMENS A&D
S7-200 Instruction
Library
USS protocol
6ES7830-2BC00-0YX0
1
Connecting cable
(direct access)
PC/PPI cable
6ES7901-3CB30-0XA0
1
USB/PPI cable
6ES7901-3DB30-0XA0
Insulation tool
PB FC stripping tool
6GK1905-6AA00
1
Spare blade cassettes (5 pieces) 6GK1905-6AB00
Optional
WinCC flexible
WinCC flexible 2004 Micro
6AV6610-0AA01-0AA0
1
Rev. A - Endgültig 23.11.2004
15:40
2/9
404963916.007.png 404963916.008.png 404963916.009.png 404963916.001.png 404963916.002.png
Easy Cabling and Cascading of Drives (with S7-200, 4x SINAMICS G110)
2
Layout Diagram
Figure 2-1
Layout diagram of the Micro Automation Set 26
Note
Standard motors with 400V/230V star/delta winding have to be connected
to the inverter in a delta connection ( 230V).
!
Warning
What should be done to prevent electromagnetic interference:
Make sure a good conductive connection between the inverter and the
(earthed) metal mounting plate is provided.
Make sure all devices in the cabinet are earthed using short earthing lines
with a large diameter and are connected to a common earthing point or
earthing bar.
Make sure the S7-200 CPU connected to the inverter is connected to the
same earthing or earthing point as the inverter using a short line with a large
diameter.
Please use shielded control lines, e.g. a SIEMENS Profibus cable for setting
up the RS485 bus.
Run control lines as far separated from power cables in separate installation
channels as possible. Crossings between power and control lines should be
at 90° angle.
Connect the protective conductor of the motor to the earth connection (PE)
of the respective inverter.
The line ends should be properly terminated and unshielded lines kept as
short as possible.
Use shielded lines for motor connections, earth the shielding both on the
inverter and the motor side using cable clamps.
Rev. A - Endgültig 23.11.2004
15:40
3/9
404963916.003.png
Easy Cabling and Cascading of Drives (with S7-200, 4x SINAMICS G110)
3
Method of Function
The configuration consists of a S7-224 XP CPU and four SINAMICS G110
drives. Visualization is provided through TP 170micro.
All SINAMICS G110 drives are coupled to the S7-224 XP CPU through a
serial RS485 interface on which the USS protocol is run. The S7-224 XP
CPU controls each individual inverter depending on the desired
performance. This makes it possible to successively switch on the drives or
to control the speed.
Moreover, precise dosing and energy-saving response are thus enabled
depending on the need. See following figures (an applicative example of
water supply):
Fig. 3-1
Applicative example: store of water
Rev. A - Endgültig 23.11.2004
15:40
4/9
404963916.004.png
Easy Cabling and Cascading of Drives (with S7-200, 4x SINAMICS G110)
The following figure shows the setpoint value of water drawing-off,
represented in the first diagram in green. The four further diagrams show
the four setpoint values of individual drives (red) depending on the setpoint
value of the water drawing-off.
(The diagrams only show the setpoint values specified by the S7-200 CPU
for the frequency inverters. The inverters use ramps parameterizable for
the start and slowdown).
Figure 3-2 setpoint values according to the performance needed
The peaks of the setpoint values of individual motors result from the fact
that a motor operation at a low speed is avoided.
If, for example, a total setpoint of 105% is predefined, motor 1 does not run
at 100% and motor 2 at 5%, it rather means that motor 1 operates at 55%
and motor 2 at 50%.