S7-1200 and STEP 7 Basic
The S7-1200 is the successor of the S7-200 and is available in June 2009. It is designed for and will
be sold in the world wide market place.
The S7-200 will remain an active Siemens product.
STEP 7 Basic v10.5 programming package (ordered separately) is used with the S7-1200
- Supports LAD and FBD. STL is not supported.
- Includes WinCC Basic for configuring HMI Basic panels.
- No separate USB license stick is required. The software is automatically activated when installed.
An export-import function for an S7-1200 project is not available in the initial release. To move
project files from one PC to another PC, use the Windows explorer and PKZIP to copy the project files
directory structure.
S7-1200 Approvals
S7-1200 hardware has the necessary approvals for the US and European market.
The S7-1200 has FM approval for hazardous location:
The Factory Mutual Research (FM): Approval Standard Class Number 3600 and 3611
Approved for use in:
- Class I, Division 2, Gas Group A, B, C, D, Temperature Class 40° C
- Class I, Zone 2, IIC, Temperature Class T4 Ta = 40° C
The S7-1200 hardware has UL and CE approvals.
S7-1200 Transition Manual
© Siemens AG 11/2009. All Rights Reserved.
A5E02486860-01
Page 1
Industry Sector
649256522.023.png
System Expandability
Hardware
EM (Expansion Module)
CP (Communication Processor)
Communication
CPU
HMI
Memory
S7-200
7 (EM + CP) maximum
Block concept
Instruction set
New data types
Timers
Counters
CM
CPU
SM (Signal Module)
Technology
Resources
S7-1200
8 SM maximum
3 CM (Communication Module) maximum
Page 2/48
S7-1200 Transition Manual
© Siemens AG 11/2009. All Rights Reserved.
A5E02486860-01
Industry Sector
S7-1200 CPU
CPU Digital I/O
CPU Analog IN
Power, Signal IN, Signal OUT
CPU 1211C DC/DC/DC
CPU 1211C
6 IN - 4 OUT
2 IN (0-10V)
CPU 1211C AC/DC/Relay
CPU 1211C DC/DC/Relay
CPU 1212C DC/DC/DC
2 IN (0-10V)
CPU 1212C
8 IN – 6 OUT
CPU 1212C AC/DC/Relay
CPU 1212C DC/DC/Relay
CPU 1214C DC/DC/DC
CPU 1214C
14 IN -10 OUT
2 IN (0-10V)
CPU 1214C AC/DC/Relay
CPU 1214C DC/DC/Relay
S7-1200 Signal Modules and Signal Boards
SM 1221 8 x 24 VDC Input
SM 1221 16 x 24 VDC Input
SM 1222 8 x 24 VDC Output
SM 1222 16 x 24 VDC Output
SM 1222 8 x Relay Output
SM 1222 16 x Relay Output
Signal Modules
SM 1223 8 x 24 VDC Input / 8 x 24 VDC Output
SM 1223 16 x 24 VDC Input / 16 x 24 VDC Output
SM 1223 8 x 24 VDC Input / 8 x Relay Output
SM 1223 16 x 24 VDC Input / 16 x Relay Output
SM 1231 4 x Analog Input
SM 1232 2 x Analog Output
SM 1234 4 x Analog Input / 2 x Analog Output
Signal Boards
SB 1223 2 x 24 VDC Input / 2 x 24 VDC Output
SB 1232 1 Analog Output
S7-1200 Communication Modules
CM 1241 RS232
CM 1241 RS485
S7-1200 Transition Manual
© Siemens AG 11/2009. All Rights Reserved.
A5E02486860-01
Page 2
Industry Sector
649256522.024.png 649256522.025.png 649256522.026.png 649256522.001.png 649256522.002.png 649256522.003.png 649256522.004.png 649256522.005.png 649256522.006.png
CPU on-board I/O and SB (Signal Board) I/O
Hardware
S7-200 CPU 224XP
S7-1200 CPU 1214C
Communication
DI Digital Input
14
14+ (2 on SB)
HMI
DO Digital Output
10
10+ (2 on SB)
Memory
AI Analog Input
2
2
AO Analog Output
1
1 on SB
Block concept
PWM / PTO
Pulse Width Modulation
Pulse Train Output
Instruction set
New data types
2
2
Timers
Counters
HSC High Speed Counter
6
6
PID Closed loop controller
8
* In planning
16
Technology
1 optional
Signal Board
(SB) can be
inserted in
the front of the
CPU
Resources
The Signal Board expands the S7-1200 CPU I/O without increasing the CPU footprint size
Page 3/48
S7-1200 Transition Manual
© Siemens AG 11/2009. All Rights Reserved.
A5E02486860-01
Industry Sector
The initial release on the STEP 7 Basic V10.5 software and S7-1200 hardware set does not include
the S7-200 expansion module types shown below. To use the S7-1200 CPU for an S7-200 application
that uses these modules, you must use a different method to replace the function of these I/O
modules. For example, there is no S7-1200 RTD or Thermocouple module. However, you can use
standard analog modules with temperature sensors. The user program can perform a linearization of
the sensor output.
S7-200 module types with no equivalent S7-1200 module (for initial S7-1200 hardware release)
EM 221 Digital 8 AC Inputs (8 x 120/230 VAC)
EM 222 Digital 8 AC Outputs (8 x 120/230 VAC)
EM 222 Digital Output (4 x Relays 10A)
EM231 Analog Input, 8 Inputs
EM231 Analog Output, 4 Outputs
EM 231 Analog Input RTD, 2 Inputs
EM 231 Analog Input RTD, 4 Inputs
EM 231 Analog Input RTD, 8 Inputs
EM 231 Analog Input Thermocouple, 4 Inputs
EM 231 Analog Input Thermocouple, 8 Inputs
EM 241 Modem module
EM 253 Position module
EM 277 PROFIBUS DP module
SIWAREX MS Micro Scale module
CP 243-2 ASi master module
CP 243-1 IT Internet module
SIMATIC TD (RS485 connection Text Display) TD 100C, TD 200, TD 200C, TD400C, OP73micro, TP177micro
S7-1200 Transition Manual
© Siemens AG 11/2009. All Rights Reserved.
A5E02486860-01
Page 3
Industry Sector
649256522.007.png 649256522.008.png 649256522.009.png 649256522.010.png 649256522.011.png 649256522.012.png 649256522.013.png 649256522.014.png
Hardware configuration S7-200
Hardware
Communication
HMI
Memory
Expansion modules are automatically recognized when connected and powered
STEP 7-Micro/WIN “SET PG/PC Interface” window configures the communication driver
STEP 7-Micro/WIN “Communications” uses the selected driver to scan and connect CPU
stations
STEP 7-Micro/WIN “System Block” window configures CPU parameters
A System Block download operation transfers the new hardware configuration into the target CPU
Block concept
Instruction set
New data types
Timers
Counters
Technology
Resources
Page 4/48
S7-1200 Transition Manual
© Siemens AG 11/2009. All Rights Reserved.
A5E02486860-01
Industry Sector
S7-1200 Transition Manual
© Siemens AG 11/2009. All Rights Reserved.
A5E02486860-01
Page 4
Industry Sector
649256522.015.png 649256522.016.png 649256522.017.png 649256522.018.png 649256522.019.png 649256522.020.png 649256522.021.png
Hardware configuration S7-1200
Hardware
STEP 7 Basic uses a visual configuration where you create an image of your actual hardware set
Hardware modules are selected from a hardware catalog tree and dragged into a rack image
After your system hardware image is assembled, use a mouse click on an item in the system image
to set the configuration “Properties” page for the selected hardware item
Select the CPU PROFINET connector on the CPU image to set the IP address properties
Use the Download command to transfer the new hardware configuration to the target CPU. When
prompted, select a network interface and CPU.
Communication
HMI
Memory
Block concept
Instruction set
New data types
Timers
Counters
Technology
Resources
Page 5/48
S7-1200 Transition Manual
© Siemens AG 11/2009. All Rights Reserved.
A5E02486860-01
Industry Sector
Password protection
S7-1200 Off-line project block password provides Know-How protection to prevent unauthorized
access to one or more of your code blocks (OB, FB, FC, or DB).
S7-1200 On-line CPU password protection provides 3 levels of security for restricting access to
CPU functions.
I/O address assignment
S7-200: I/O addresses automatically fixed by CPU operating system according to module location.
S7-1200: Default I/O assignment can be modified by Device configuration properties.
S7-1200 Transition Manual
© Siemens AG 11/2009. All Rights Reserved.
A5E02486860-01
Page 5
Industry Sector
649256522.022.png