Wejście binarne 8 kanałów 12-35 V DC z izolacją wejśd
Wersja BETA English
Object
Name
Function
Type
Flag
Function: Switching (for all inputs)
0 – 7
Input1 – 8
Switching
1 Bit
C, W, T, (R)
Function: Dimming (for all inputs)
0 – 7
Input 1 – 8
Switching
1 Bit
C, W, T, (R)
8 – 15
Input 1 – 8
Dimming
4 Bit
C, T, (R)
Function: Blind/shutter control (for all inputs)
0 – 7
Input 1 – 8
Short time operation
1 Bit
C, T, (R)
8 – 15
Input 1 – 8
Long time operation
1 Bit
C, T, (R)
Function: Dimming value transmitter (for all inputs)
0 – 7
Input 1 – 8
Value
1 Byte
C, T, (R)
Function: Light scene extension (for all inputs)
0 – 7
Input 1 – 8
Light scene extension
1 Byte
C, T, (R)
Function: Temperature value transmitter (for all inputs)
8 – 15
Input 1 – 8
Temperature value
2 Byte
C, T, (R)
Function: value transmitter (for all inputs)
8 – 15
Input 1 – 8
Brightness value
2 Byte
C, T, (R)
Function: Impulse counter (for inputs 1 and 2 only)
2
Input 3
Synch signal counter 1
1 Bit
C, W, T, (R)
3
Input 4
Synch signal counter 2
1 Bit
C, W, T, (R)
8
Input 1
Meter reading counter 1
2 Byte
C, T, (R)
9
Input 2
Meter reading counter 2
2 Byte
C, T, (R)
Function: Switching counter (for inputs 1 and 2 only)
0
Input 1
Switching counter
1 Bit
C, W, T, (R)
1
Input 2
Switching counter
1 Bit
C, W, T, (R)
8
Input 1
Switching counter
2 Byte
C, T, (R)
9
Input 2
Switching counter
2 Byte
C, T, (R)
Function: Blocking (for all inputs)
16 – 23(*)
Input 1 – 8
Blocking
1 Bit
C, T, (R)
I
INTELEKTRONIK 32-400 Mylenice ul Średniawkiego 104c
Strona 1
Objects marked with (R):
Object value can be read out (set R-flag!)
Objects marked with (*):
If the inputs have been parameterised to "no function", "impulse counter" or "switching counter", the blocking function is not active.
Impulse counter:
The pulse counters can only be parameterised to input 1 or 2. In this case, inputs 3 (for pulse counter 1) or 4 (for pulse counter 2) are the
sync signal inputs and cannot be assigned to any other function. Pulse counters 1 and 2 run independently of each other and have a
resolution of 16 bit so that counts between 0 and 65535 are possible. You can set the R-flag to read out the current count at object 8 or 9.
The counting pulse is applied to input 1 or 2. After the interval time specified as parameter has elapsed, the count will be taken over and
sent as object value of the 2 byte "count" object (object 8 or 9). Then the 2 byte pulse counter will be internally reset during the next time
interval.
Only upon the appearance of a new edge at the input, or after the newly started interval time has elapsed, the current count can be read
out from the count objects (set R-flag).
In addition, the count and the interval time can be reset by a sync signal applied to input 3 or 4, respectively. Moreover, switch telegrams
(no telegram, ON, OFF, TOGGLE) can be sent in dependence of the sync signal edge. The output value can be assigned to the edge.
The edge assignment for resetting the count can be parameterised independently of the output value.
For pulse counting, the mark-to-space time of a signal applied to input 1 or 2 must not fall below 100 ms.
Fig.1 Impulse counter
Switching counter:
The switching counters can only be parameterised to input 1 or 2. Switching counters 1 and 2 run independently of each other and have a
resolution of 16 bit so that counts between 1 and 65535 are possible. You can set the R-flag to read out the current count at object 8 or 9.
The counting pulse is applied to input 1 or 2. After the count has reached the parameterised set value, it will be taken over into 2 byte
object 8 or 9 and transmitted. Simultannously, it is possible to output a signal value (1 bit object "0" or "1") which can be parameterised.
After the transmission, the 16 bit counter will be automatically and internally reset. Only upon the appearance of a new edge at the input,
the current count can be read out from the count objects (set R-flag).
Moreover, the count will be sent in cycles after a pre-defined number of counting pule (1 255), which i ued to get an automatic
update on any display for instance.
For switch counting, the mark-to-space time of a signal applied to input 1 or 2 must not fall below 100 ms.
Fig.2 Switching counter
I
INTELEKTRONIK 32-400 Mylenice ul Średniawkiego 104c
Strona 2
Blocking function:
At the beginning or at the end of the blocking, an independent response can be made to each input. In this case, you can set the parameter
to "no response". Only in such case, any dimming or blind/shutter control or value changing events running until the action is completed
during an active blocking. In any other cases, the parameterised command will be sent immediately at the start of blocking. Moreover, any
edges or signals at the corresponding inputs will not be accepted during an active blocking.
Updates on blocking objects (disable or enable) each time cause the corresponding parameterised command to be sent "at start or end of
the blocking".
During an active blocking, there will be no cyclic sending through the disabled input.
If cyclic sending was taking place prior to an activation of the blocking function, no more cyclic sending will be performed at the end of the
blocking, provided that "no telegram" has been parameterised. In this case, the cyclic transmission of the object value will only be effected
again after an update on the switching object. In any other cases, the object value will be sent in cycles again after the end of blocking.
Intelektronik Wejcie binarne 8, Wersja 1.0
I
INTELEKTRONIK 32-400 Mylenice ul Średniawkiego 104c
Strona 3
Plik z chomika:
tarnel
Inne pliki z tego folderu:
INT_2Kanal_Dimmer.pdf
(441 KB)
INT_2Kanal_Dimmer_LED.pdf
(440 KB)
INT_4Kanal_Output.pdf
(463 KB)
INT_8Binary_Input.pdf
(393 KB)
INT_8Kanal_Output.pdf
(463 KB)
Inne foldery tego chomika:
• Mikrokontrolery i układy cyfrowe
Automatyka
Chłodnictwo i klimatyzacja
dokumentacja_PLCSim
Mechanika automatyki przemysłowej i urządzeń precyzyjnych
Zgłoś jeśli
naruszono regulamin